Download Generator and Controls
Transcript
FLOW CHART D. EXCITER FIELD BREAKER TRIPS STANDARD VOLTAGE REGULATOR START kyes-l I I I 1 I 1 1 Check for any loose or broken wires or connections on VR21 assembly. Does AC output voltage build up to 15O0/o0r more of rated voltage before breaker trips? 1 Check diodes and SCR's in bridge assembly CR21 per TEST [C]. Check reference transformer T21 and connections per TESTS [E] and [a]. Replace if bad. Check exciter stator winding per TEST [HI. Replace if bad. I v I Check generator stator leads for proper connection. See Figure 26. Check exciter rotor winding per TEST [J]. Replace if bad. I I I 1 , Check generator rotor field winding per TEST [L]. Replace if bad. I b 1 Check generator stator windings per TEST [K]. Replace if bad. Test voltage regulator assembly per procedure (S). Replace the regulator PC board per procedure (F)if defective. The new printed circuit board might be damaged by malfunctioning components within the control. Do not install the new PC board until all other problems have been located and corrected. 18 Redistribution or publication of this document, by any means, is strictly prohibited.