WARNING Hazards present in troubleshooting can cause equipment damage, severe personal injury or death. Only trained and experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Read Safety Precautions page and observe all instructions and precautions in this manual. CODE 14 - OVER FREQUENCY (SHUTDOWN) Reason: Generator AC output frequency is high. Effect: Generator set will shut down. POSSIBLE CAUSE CORRECTIVE ACTION 1. Fault threshold is not set correctly with PC based service tool. 1. Reset the threshold to the highest allowable setting. Determine the required operating range before adjusting the threshold. 2. Fuel or air delivery problem. 2. Refer to the engine service manual. 3. Governor fault. 3. Check governor frequency adjustment (Refer to Section 7). 4. Loose connector or Base board is bad. 4. Repair connections (P12/P13) or replace the Base board if necessary. CODE 15 - UNDER FREQUENCY (SHUTDOWN) Reason: Generator AC output frequency is low. Effect: Generator set will shut down. POSSIBLE CAUSE 1. Fault threshold is not set correctly with PC based service tool. CORRECTIVE ACTION 1. Reset the threshold to the lowest allowable setting. Determine the required operating range before adjusting the threshold. 2. Overload. 2. Check the load and correct any overload. Check operation by disconnecting load and restarting generator set. 3. Fuel or air delivery problem. 3. Refer to the engine service manual. 4. Governor fault. 4. Check fuel shutoff solenoid adjustment. 5. Loose connector or Base board is bad. 5. Repair connections (P13) or replace the Base board if necessary. 4–16