Installation 2.3 Mounting the System (Continued) The USonic-R is designed for field mounting, but it should be mounted in a location as free as possible from vibration, corrosive atmospheres, and any possibility of mechanical damage. For convenience when adjusting and configuring, place the USonic-R Series in a reasonably accessible location. Ambient temperature should be between -40°F to 158°F (-40°C to 70°C). The Sensing Element must be mounted vertically and perpendicular to the liquid surface. When mounting the USonic-R Series Sensing Element, consideration must be given to the 12-Inch (305 mm) Near Zone. If the level rises to within 12 inches (305 mm) of the Sensing Element face, a user selectable 3.7 mA or 22 mA error signal is generated; Error message ( ) is indicated. The conical beam of the USonic-R Series is approximately 10 degrees. Therefore it is necessary to ensure that there are no unnecessary obstructions within this beam path. Erroneous reflections can adversely affect system operation. DEAD ZONE DEAD ZONE 5˚ 5˚ Mounting Recommendations For Open Channel Flow use, an optional mounting kit is available for mounting above a flume or weir to position the system above the flow stream. The mounting kit allows movement vertically and horizontally for maximum placement. • Part # 285-0001-188 (316 SS) Refer to drawings 285-0001-188-CD for Mounting Details. 7