Download DL305 User Manual

Transcript
7–15
Discrete Output Modules
F3–16TA–2, 20–125 VAC Output Module
Outputs per module
Commons per module
16
2 (isolated)
Operating voltage
20 – 125VAC
OFF to ON response
ON to OFF response
Terminal type
Status indicators
Weight
Fuses
(One spare fuse
included)
SSR Array (TRIAC)
140 VAC
47 – 63Hz
1.1VAC @ 1.1A
1.1A / point
0.7mA @ 125VAC
15A for 20ms
8A for 100ms
Points
50mA
9V 14mA / ON pt.
250mA Max.
24V N/A
8ms Max.
8 ms Max.
Removable
Logic Side
7.7oz. (218g)
4 (One 5A 125V fast
blow per each group
of four outputs)
Order D3–FUSE–4
(5 per pack)
Discrete Output
Modules
Output type
Peak voltage
AC frequency
ON voltage drop
Max current
Max leakage current
Max inrush current*
Minimum load
Base power required
Derating Chart
16
1.0A
0.5A
12
1.1A
8
20–125VAC OUTPUT
4
F3––16TA––2
0
0
32
10
20
30
40
50
60 C
50
68
86
104 122 140 F
Ambient Temperature (degrees C / F)
*Fuse blows at 20 Amp surge
Motor starters up to and including
a NEMA size 3 can be used with
this module.
20–125VAC
H
I
L
0
L
1
2
L
L
3
4
L
L
20–125VAC
5
6
L
7
H II
L
0
L
1
L
3
L
5
L
7
L
2
L
4
L
6
5A
20–125VAC
Common
L
Output
5A
To other 4 circuits
To other 3 circuits
9V
0
1
2
3
I H
0 I
1
2
3
4
5
6
7
H
II
0
1
2
3
4
5
6
7
II
4
5
6
7
0
1
2
3
4 II
5
6
7
Discrete Output
Modules
L
I