8–15 System Operation Normal Maximum I/O Response The I/O response time is longest when the module senses the input change just after the Update I/O portion of the execution cycle. In this case the new input status does not get read until the following scan. The following diagram shows an example of the timing for this situation. Scan Scan Solve Program Solve Program Solve Program Solve Program Update I/O Field Input CPU Reads InĆ put change CPU Writes Output change Input Module Off/On Delay Output Module Off/On Delay I/O Response Time Improving Response Time There are a few things you can do the help improve throughput. S You can try to choose instructions with faster execution times S You can choose modules that have faster response times System Operation In this case, you can calculate the response time by simply adding the following items. Input Delay +(2 x Scan Time) + Output Delay = Response Time