Download 1S24 User's Guide

Transcript
Trip 2
Yes or No, determines if the Sensor input operates the Trip 2 output, click on the field to change
the state and enter the user name and password if prompted.
Zone
The Zone Setting provides a means of improving Goose response time for simultaneous trips in a
single Arc Fault tripping zone. The Zone setting ensures that a Goose is immediately broadcast
without having to wait for the updating of all arc detectors in the same corresponding zone.
Allowable Zone values are from 1 to 16. Set the Zone value the same for sensors located in the
same zone. Click on the field to alter the Zone value.
Arc Status
The Arc Status screen provides status information on each of the of the 16 Sensor inputs.
Page 21
Visit
www.rmspl.com.au
for the latest product information.Page
Due to RMS continuous product improvement policy this information is subject to change without notice. 1S24_Guide/Iss B/23/07/12