Valid for the 8 zones exp. board 4580 zone line input x (xxx-xx =
zone – address). The board is mounted in control unit xx.
Break on the zone line, wrong / no end-of-line device / short-circuit (if
not programmed for fire alarm at short-circuit).
FAULT: Zone line input, xxx-xx
technical number xxxxxx
Valid for the Multipurpose I/O unit 3361 monitored zone line input Z.
Break on the zone line or wrong / no end-of-line capacitor (470 nF) or
short-circuit (if not programmed for fire alarm at short-circuit).
No contact with main board
Fault in the Main board 5010 software or the Main board. Check the
cable between the boards. This is a very serious fault. Call for service
personnel/engineer immediately.
(User programmable text; External fault)
Programmable input is connected to any external equipment's fault
output. User definable fault message programmed via WinG3.