Download User Manual - Data 2000 Sistemas

Transcript
Piccolo Range
2.6
User Manual
Output 1
This output is available in all models and can be logic (SSR drive), or relay, depending on the order code.
For output functions, see Quick Start Code in section 4.1.1 or ‘P’ Codes in section 5.2.
2.6.1
2.6.2
Relay Output (Form A, normally open)
1A
• Isolated output 300Vac CAT II
1B
• Contact rating: 2A 230Vac +15% resistive
Logic (SSR drive) Output
1A
1B
• Isolated output 300Vac CAT II
+
• Output ON state: 12Vdc at 40mA max
-
• Output OFF state: <300mV, <100μA
• The output switching rate must be set to prevent damage to the output device
in use. See parameter 1.PLS in section 4.7.2.
2.7
Output 2
Output 2 is available in all models.
In P116 it can be ordered as Relay, Analogue or Triac.
In P108 and P104 it can be ordered as Relay or Triac.
For output functions, see Quick Start Code in section 4.1.1 or ‘P’ Codes in section 5.2.
2.7.1
2.7.2
Relay Output (Form A, normally open)
2A
• Isolated output 300Vac CAT II
2B
• Contact rating: 2A 230Vac +15% resistive
DC Output (P116 only)
2A
2B
• Output isolated 300Vac
+
• Software configurable: 0-20mA or 4-20mA.
-
• Max load resistance: 500Ω
• Calibration accuracy: +(<1% of reading + <100μA)
2.7.3
Triac Output
2A
• Isolated output 300Vac CATII
2B
• Rating: 0.75A rms, 30Vac (minimum) to 230Vac +15% resistive
Part No HA031260
Issue 1 May-12
13