Specification
Type
Rated output at 80/60 °C
Rated output at 50/30 °C
Rated heat input
Lowest output (modulating at 80/60)
Lowest output (modulating at 50/30)
Lowest heat input (modulating)
External diameter, heating flow
External diameter, heating return
Drain outlet (condensate)
Gas connection
Balanced flue connection
Appliance dimensions HxWxD
Balanced flue routing
Gas category:
Gas supply details:
Natural gas H (Hi = 9.5 kWh/m³ = 34.2 MJ/m³)
LPG P (Hi = 12.8 kWh/kg = 46.1 MJ/kg)
Gas supply pressure:
Natural gas
LPG
Flow temperature, factory setting
Maximum flow temperature
Max. overall pressure, heating
Heating water heat exchanger water content
DHW temperature range (adjustable)
Heating water pressure drop at 20 K spread
Rated output:
Flue gas mass flow rate
Flue gas temperature 50/30 - 80/60
Available gas fan draught
Lowest heat input:
Flue gas mass flow rate
Flue gas temperature 50/30 - 80/60
Available gas fan draught
Flue gas group according to DVGW G 635
NOx category
Electrical connection
Integral fuse (medium slow)
Power consumption
Protection
Total weight (dry)
Condensate volume at 40/30 °C
Condensate pH value
CE ID
ÖVGW quality symbol
3062555_201507
CGB-75
70.1
75.8
71.5
18.2
19.6
18.5
1½"
1½"
1"
¾"
110/160
1020x565x548
B23, B33,
C13, C13x
C33, C33x
C43, C43x
C53, C53x
C63, C63x
C83, C83x
C93, C93x
II2H3P
CGB-100
91.9 2)
98.8
94
18.2
19.6
18.5
1½"
1½"
1"
¾"
110/160
1020x565x548
B23, B33,
C13, C13x
C33, C33x
C43, C43x
C53, C53x
C63, C63x
C83, C83x
C93, C93x
II2H3P
m³/h
kg/h
7.77
5.76
10.03
7.44
mbar
mbar
°C
°C
bar
l
°C
mbar
20
37/50
80
90
6
10
15-65
70
20
37/50
80
90
6
10
15-65
120
g/s
°C
Pa
33.7
48-72
145
43.5
53-78
200
g/s
°C
Pa
8.9
36-60
12
G52
5
230/50
3.15
75
IPX 4D
92
7.1
approx. 4
8.9
36-60
12
G52
5
230/50
3.15
130
IPX 4D
92
9.8
approx. 4
kW
kW
kW
kW
kW
kW
G
G
R
mm
mm
type
V~/Hz
A
W
kg
l/h
0085BR0164
G 2,775"