Download manual
Transcript
Step Display Description 9 FCUT Frequency Cutoff prevents display and integration of the frequency input below xxxHz. Limited to 125Hz. XXX 10 F dPt Number of decimal points with which the Rate is to be displayed between 0 to 0.00000. 11 t.base 60secs hours The Timebase with which the Rate is calculated must be entered as: units/min units/hour 12 FILTER The filter constant for filtering the rate display. 1 to 99 No filtering. Very heavy filtering. If the Preset is disabled, Step 13 is the Timeout. If Preset is enabled, the Timeout will be entered when entering the Batch Parameters. 13 TOUT The Signal Timeout in seconds (setting to 00 disables this feature). 14 t.dPt Number of decimal points with which the Net (resettable) total is displayed between 0 to 0.000. 15 A.dPt Number of decimal points with which the Accumulated (non resettable) total is displayed between 0 to 0.000. 16 t.c. none petrol LPG genliq An_nH3 The type of Temperature Compensation can be selected as follows: No temperature compensation. Compensation for Petroleum products. Compensation for Liquid Petroleum Gas. Volume Correction for General liquids. Compensation for Anhydrous Ammonia. If "none" (no temperature compensation) is selected the program will go to Step 25. All other selections result in the following steps being displayed: 17 t. °F °C Select either US units or metric units as the basis of the temperature compensation. US units. Metric units. With a direct RTD input, the temperature can be adjusted (offset) to correct for the RTD tolerance. 18 ADJ t xx.xx Adjust the temperature displayed during Test. Input the offset. (The first digit is 0 for positive or - for negative.) This is for fine adjustment only and is limited to +/- 0.3 of a degree. 15