Download Simplex 4100U Installation manual
Transcript
SIMPLEX 4100 FIRE INDICATOR PANEL OPERATOR MANUAL Page 35 Pressing function key <F1> will turn on the LED indicator on the selected smoke detector and as long as the function key is depressed. Press the <NEXT> key to move onto the next display. Level 3 - Room 74 Smoke Detector ON-LINE Press the <NEXT> key to move onto the next display to verify correct device type: Level 3 - Room 74 Smoke Detector Correct Device Press the <NEXT> key to display the current selected sensitivity Level 3 - Room 74 Present Sensitivity Selected - 3.7% Smoke To view the average value of samples received from the sensor press the <NEXT> key again Level 3 - Room 74 Average Value = 75 / Alarm Level - 135 This is the present average of the last 2048 samples received from the sensor. The Alarm Level is the binary value that is used to determine alarm conditions. This value will change over time as the panel compensates for environmental conditions. This value will be different for each of the (7) sensitivity levels. To view the last binary value that was received from the sensor press the <NEXT> key again Level 3 - Room 74 Value = 75 / 6% of Alarm / 0.1% Smoke This value is displayed as a % of alarm and a % of smoke obscuration. Document No: 4100-M001 May 1997 Issue 1.0