Installation and Operating Instructions
13
T E C H N I C AL
D AT A
SDC 306
Housing
Material
100% recyclable ABS casing for wall-mounted installation
Dimensions (H x W x D) in mm, 175 x 134 x 56; approx. 360 g
weight
Protection class
IP20 in accordance with VDE 0470
Electrical values
Operating voltage
AC 230 Volt, 50 Hz, -10...+15%
Internal device fuse
Micro-fuse 5 x 20mm 2 A/surge-proof
Radio interference level
N in accordance with VDE 0875
Maximum cable cross-section
230 V connections
2.5 mm² fine-strand/single-strand
Temperature sensor /
temperature range
PTF6 - 25°C - 200°C
PT1000, 1.000 kΩ at 0°C
Testing voltage
4 kV 1 min in accordance with VDE 0631
Switching output
Output depending on switching
output
Total output for all outputs
230 V∼ /
1 A / approx. 230 VA for cos ϕ = 0.7-1.0
2A/ approx. 460 VA
Fuse protection
Micro-fuse 5 x 20 mm, 2 A/T (2 amp, fine-wire)
Other
Recommended flow meter
PVM 1.5/90 1500l/h, Tmax >=90°C, 10l/impulse
Operating temperature
0 ... + 50°C
Storage temperature
-10 ... + 65°C
14 R E S I S T AN C E
T AB L E
PT1000
The correct function of the temperature sensor can be checked against the following
temperature resistance table, using a resistance measurement device:
Temperature
Resistance (Ohms)
Temperature
Resistance (Ohms)
in °C
in °C
-30
882
60
1232
-20
921
70
1271
-10
960
80
1309
0
1000
90
1347
10
1039
100
1385
20
1077
120
1461
30
1116
140
1535
40
1155
200
1758
50
1194
Manufacturer of SDC 306 control unit devices: PROZEDA GmbH
SDC 306
1316BED036-11B-E
- 54 -
Date 06/09