FST Configuration
IFTOSS
4Ć105
IFTOSS
51
INSTRUCTION NAME: IFTOSS (if true, operator station secondary point)
DESCRIPTION: This instruction switches the operator station specified by operand 2 to the
secondary DCP based on the logical state of the logic value specified by operand 1. This function
is used with double or cascade operator station types. The SVA and SVD inputs remain
unchanged.
CONFIGURATION FORMAT: IFTOSS (
Logic signal
Operator station port #
Comment
>>
>>
>>
OPERAND DESCRIPTIONS:
Logic signal - The name of the general register or discrete loadable function that contains the
logic value.
Operator station port # - The number assigned to the operator station. See Operator Station
definition section, Table 4Ć2 on page 4Ć9 for possible operator station port numbers for each
controller type.
Comment - A comment up to 255 characters long.
FUNCTION EQUATIONS:
If logic value = 0
Then selected DCP is unchanged
If logic value = 1
Then Secondary DCP is selected
SVA(out) = SVA(in)
SVD(out) = SVD(in)
Original Ć June 1990
CE4.2:CL6211