Download Response Electronics CL6011B Specifications
Transcript
FST Configuration INT 4Ć109 INT (Continued from previous page) OPERAND DESCRIPTIONS: Integrator gain - A tuning parameter value in units of repeats per minute. The gain is any non-negative floating point number. For a constant input, the output will change by the input value multiplied by the integrator gain per minute. Initial condition - The name of the general register or analog loadable function that contains the analog value used as the SVA output when the value in operand 3 is 1. Reset signal - The name of the general register or discrete loadable function that contains the reset value. (Logic 0 = normal integration, logic 1 = reset to initial value specified in operand 2) Comment - A comment up to 255 characters long. CONFIGURATION EXAMPLE: INT (2.9, AIN (1), DI (1)) FUNCTION EQUATIONS: If Reset signal = 0, Then SVA(out) = HA + [(TP X Dt) X SVA(in)] Where: HA = SVA(out) last cycle TP = Integrator gain in repeats per minute (operand 1) Dt = Sample time in minutes If Reset signal = 1, Then SVA(out) = Analog value in operand 2 SVD(out) = SVD(in) On power up: SVA(out) = HA = Analog value in operand 2 SVD(out) = SVD(in) Original Ć June 1990 CE4.2:CL6211