Register Name Address Description BAUDRATE 40007 Designates the baud rate used by the MODBUS interface. After modifing this register, a gateway reset must be performed before changes can take effect. Value Represented 0 1 2 3 (DEFAULT) 4 5 6 COMMODE 40008 Designates the operating mode used by the MODBUS interface. After modifing this register, a gateway reset must be performed before changes can take effect. Value Represented 0 1 (DEFAULT) 2 3 4 5 6 ADDRESS 40009 Baud Selected 2400 4800 9600 19200 38400 57600 115200 Meaning RTU : 8-N-2 RTU : 8-N-1 RTU : 8-E-1 RTU : 8-0-1 ASCII : 7-N-2 ASCII : 7-E-1 ASCII : 7-O-1 Designates the MODBUS Address used in the communications interface. Values range from 1-247. Default value is 99. Modifying this register will result in a gateway reset. Once you have written your new settings, you will have to perform a reset for the settings to take effect. To perform a reset, write the “RST_DEVICE” Gateway Coil @ address 3 to TRUE. The device will reset one second after receiving this command. Your new communication settings will be in effect. To verify them, attempt to read the Gateway ID from registers 40002 - 40003 PAGE 5