Download - CyberResearch
Transcript
M-7015 3.3.9 Sub-function 38 (0x26) Set channel enable/disable This sub-function code is used to specify the channels to be enabled in a module. Request 00 01 02 03 Address 1 Byte Function code 1 Byte Sub function code 1 Byte Enable/disable 1 Byte 1 to 247 0x46 0x26 0x00 ~ 0x3F, enable/disable setting of each channel, where bit setting 0 corresponds to channel 0, bit 1 corresponds to channel 1, etc. When the bit is 1 it denotes that the channel is enabled and 0 denotes that the channel is disabled. Note: This sub-function is only applicable to the M-7015. Response 00 01 02 03 Address Function code Sub function code Enable/disable setting 1 Byte 1 Byte 1 Byte 1 Byte 1 to 247 0x46 0x26 0: OK others: error. Error Response 00 01 02 128 Address Function code Exception code 1 Byte 1 Byte 1 Byte 1 to 247 0xC6 03: enable/disable setting out of range, incorrect number of bytes received CM 7013/15/33, M-7015/33 User’s Manual, Rev: B1.7 7PH-008-B17