CM 7013, CM 7013D, CM 7013, M-7015
Examples:
Command: $014
Response: ?01
Reads the synchronized data for module 01. An
invalid command is returned because the #**
command has not been issued in advance.
Command: #**
No response
Sends the synchronized sampling command.
Command: $014
Response: >011+025.56
Reads the synchronized data for module 01. The
module returns the synchronized data and sets the
status byte to 1 to indicate that this is the first time
the synchronized data has been read.
Command: $014
Response: >010+25.56
Reads the synchronized data for module 01. The
module returns the synchronized data and sets the
status byte to 0 to indicate that the synchronized
data has been read.
Related Commands:
Section 2.2 #**
Notes:
This command is only applicable to the CM 7013, M-7015
and CM 7013/13D.
CM 7013/15/33, M-7015/33 User’s Manual, Rev: B1.7 7PH-008-B17