Download CommPAK I/O8 - Encom Wireless

Transcript
CommPAK I/O8
Wireless On/Off Control USER MANUAL
Using Traffic Controller Outputs as
Input Connections with the I/O8
Radio
For example, if we are programming the
outputs of another COMMPAK I/O8 the
programming for the I/O configuration would
be shown below:
The following application shows you how to
connect a Traffic Controller to the Input
Connection of an I/O8 Radio.
A Traffic Controller is an example of a device
with Open Collector Outputs. Refer to the User
Manual of your Traffic Controller or other
equipment to determine if it is configured with
Open Collector Outputs.
The Controller Equipment open collector
outputs are to have a Pull Up Resistor (10K
ohm) installed. The Controller Equipment signal
ground must be connected to the COMMPAK
I/O8 ground.
The Output 1 of our Remote Radio is going to be
activated by Radio address 0 (this being our
Master radio with the Open Collector input
relay) and the corresponding Input number.
Any Input can activate any Output.
Connect each Controller Equipment open
collector output to the COMMPAK I/O8 Inputs
as shown below:
For more information on configuring refer to
the section on Configuring Your I/O8 Radio.
You do not have to “program” the Inputs in the
ControlPAK software. The programming is only
on the Outputs of the either this radio or
another radio.
The Outputs are programmed so that the
installed Open Collector Input is used as the
activation switch for your system.
Page 24
© 2009 Encom Wireless Data Solutions. All Rights Reserved