Download 100140-010 PMD-4 User Manual Draft (2)
Transcript
Annual Warning Time Retest Procedures The purpose of this procedure is to provide a method for reducing the time and effort needed to perform the required FRA annual warning time tests. This is accomplished by identifying all critical site specific switch and adjustment settings, which can affect warning time, and assigning a single comprehensive CRC value hereafter called the Warning Time CRC (WT CRC). The process of accomplishing this is to initially setup, test and document the operation of the warning system. When testing has been satisfactorily completed, a Warning Time CRC value is generated from the combined internal settings of the PMD-4 for the specific site. The resulting unique Warning Time CRC number simplifies the verification of all of these settings. This Warning Time CRC can be compared to later inspections to determine, conclusively, if any site specific setting has been changed since the unit was last operationally verified and documented. . If the two numbers agree, it is certain that no critical PMD-4 parameters have been changed that would affect warning time. Provided that the Warning Time CRC and additional display values specified below match their recorded values within specified limits, the unit can be safely recertified. The following verification form specifies the items that should be checked to verify the warning time periodically after initial installation. Base testing values should be captured upon initial installation or upon recertification of warning time operation. Mark any not applicable items as NA. If the values differ from the specified ranges, then the original process of initial setup, test, and documentation should be performed. Periodic Warning Time Test Form For PMD-4/4R Location Equipment Parameter RX Site Specific Parameters PMD-4/4R Parameters to Verify Type of Setting RX is within 95 to 105 (91 to 109 if Auto RX is disabled) and is stable +/- one digit. Displayed value Verify the Warning Time CRC value from the CDU or web GUI matches base testing value as recorded on the Grade Crossing Location Record form. Display Value Base testing values Current test Current test - Standby - Normal Units units External Wiring Activate the crossing then verify the crossing warning devices all operate as intended. NA NA Remote Starts Verify that the remote start control activates all crossing warning devices as intended. NA NA