Process Control Instruction
331
Automatic / Manual (AM)
Tuning Parameter
Descriptions
AM - Automatic/Manual
Address
Data Format Range
Type
PD10:0/AM
binary (bit)
control
0 or 1
User Program
Access
read/write
The auto/manual bit can be set or cleared by instructions in your ladder
program. When off (0), it specifies automatic operation. When on (1), it
specifies manual operation. In automatic operation, the instruction
controls the control variable (CV). In manual operation, the user/control
program controls the CV. During tuning, set this bit to manual.
TIP
Output limiting is also applied when in manual.
Control Mode (CM)
Tuning Parameter
Descriptions
CM - Control Mode
Address
Data Format
Range
Type
PD10:0/CM
binary (bit)
0 or 1
control
User Program
Access
read/write
Control mode, or forward-/reverse-acting, toggles the values E=SP-PV and
E=PV-SP.
Forward acting (E=PV-SP) causes the control variable to increase when
the process variable is greater than the setpoint.
Reverse acting (E=SP-PV) causes the control variable to decrease when
the process variable is greater than the setpoint.
PV in Deadband (DB)
Tuning Parameter
Descriptions
DB - PV in Deadband
Address
Data Format
Range
Type
PD10:0/DB
binary (bit)
0 or 1
status
User Program
Access
read/write
This bit is set (1) when the process variable is within the zero-crossing
deadband range.
Publication 1762-RM001F-EN-P - October 2009