Process Control Instruction 331 Automatic / Manual (AM) Tuning Parameter Descriptions AM - Automatic/Manual Address Data Format Range Type PD10:0/AM binary (bit) control 0 or 1 User Program Access read/write The auto/manual bit can be set or cleared by instructions in your ladder program. When off (0), it specifies automatic operation. When on (1), it specifies manual operation. In automatic operation, the instruction controls the control variable (CV). In manual operation, the user/control program controls the CV. During tuning, set this bit to manual. TIP Output limiting is also applied when in manual. Control Mode (CM) Tuning Parameter Descriptions CM - Control Mode Address Data Format Range Type PD10:0/CM binary (bit) 0 or 1 control User Program Access read/write Control mode, or forward-/reverse-acting, toggles the values E=SP-PV and E=PV-SP. Forward acting (E=PV-SP) causes the control variable to increase when the process variable is greater than the setpoint. Reverse acting (E=SP-PV) causes the control variable to decrease when the process variable is greater than the setpoint. PV in Deadband (DB) Tuning Parameter Descriptions DB - PV in Deadband Address Data Format Range Type PD10:0/DB binary (bit) 0 or 1 status User Program Access read/write This bit is set (1) when the process variable is within the zero-crossing deadband range. Publication 1762-RM001F-EN-P - October 2009
Related documents
1762-RM001 - Rockwell Automation
MicroLogix™ 1200 and MicroLogix 1500 Programmable Controllers
1769-UM006 - Rockwell Automation
KDN-K3 CPU支持的数据类型位串类型及数值类型两种
Allen-Bradley 1794-IE8H Specifications
1762-RM001B-US-P, MicroLogix™ 1200 and MicroLogix 1500
Arquivos de Dados - Apostilas técnicas
1763-RM001 - Rockwell Automation
Compact I/O 1769-ADN DeviceNet Adapter
Additional Resources
1769-UM001 - Rockwell Automation
Multi-Channel High Speed Counter