Download chlorine
Transcript
SPI – C 170 CHLORINE 8. m3/h at 30Hz (Set the amount of cubic litres of water each hour when the flowmeter sends out pulses of 30hz. Only valid when you chose a flowtype with pulse output. See chapter 11.3.1) 9. m3/h at 100% (Set the amount of cubic litres of water each hour when the flow is 100% This information should be supplied with the design plan by the installer) 10. m3/h at 20mA (Set the amount of cubic litres of water each hour when the flowmeter sends out 20mA. Only valid when you chose a flowtype with current output. See chapter 11.3.1) 11. Cell contamination (Set the minimum zero measurement at which an alarm should be given to identify starting pollution of the cell, a small ‘v’ then appears behind Overview in the overview menu) m3/h m3/h m3/h Cell at 30Hz at 100% at 20mA contam. : : : : 50 100 100 800 Figure 16.1.1. 12. Cell dirty (Set the minimum zero measurement at which an alarm should be given to identify complete pollution of the cell, a capital ‘C’ then appears behind Overview in the overview menu) 13. Cell alarm delay (Set the time in seconds the system delays the alarm of starting and complete pollution) 14. System ID (Set a custom identification number to this SPI for recognition. The numbers 1 – 254 can be used) 15. Alarm at night (Set here if you want alarms to be activated at night (1) or not (0)) Cell dirty : Cell alarm del: System ID : Alarm at night: 600 900 123 1 Figure 16.1.1. 16. pH mode (Set here if you’d like to use either acid (0) or lye (1) to control the pH of the water, the pH controls will be reversed then) 0)acid 1)lye pH mode : Min rea. Valve: Beep On/Off : 0 5 1 Figure 16.1.1. V1 20130904 53