107
Communication item Used/Not used selection
flag
Determines every 1 bit of word data.
(1: Used, 0: Not used)
108
Determines a Set value change flag.
109 to 119
120 to 129
Spare
Main set value (SV)
130 to 139
Main proportional band
140 to 149
Integral time
150 to 159
Derivative time
160 to 169
Alarm 1 (High limit)
170 to 179
Alarm 2 (Low limit)
180 to 189
Main output proportional cycle
190 to 199
Heater burnout alarm
210: Loop break alarm 2 time
211: Cooling proportional band
212: Cooling proportional cycle
213: Overlap band/Dead band
214: Cooling action mode
215: Cooling output ON/OFF action
hysteresis
20: PV reading
21: MV reading
22: Heater current value reading
23: Current status 1 reading
24: Current status 2 reading
25: CPU version number reading
26: Instrument status reading
27 to 215:
0: No change
1: All setting items change
2: Main set value change
3: Alarm 1 and 2 and Heater burnout
alarm value change
4: Main proportional band,
Integral time, Derivative time,
Cooling proportional band and
Overlap band/Dead band change
5: Auto-tuning change
6: Control output Perform/Stop change
7: Alarm action 1 and 2,
Main proportional cycle and
Cooling proportional cycle change
8: Control output high and low
limit value change
Main set value from Ch1 to Ch10
Setting range: See “Rated scale” in
Chapter 11. Specifications (Page.91)
Main proportional band from Ch1 to
Ch10
Setting range: 0.0 to 100.0%
Integral time from Ch1 to Ch10
Setting range: 0 to 3600 sec.
Derivative time from Ch1 to Ch10
Setting range: 0 to 3600 sec.
Alarm 1 (High limit) set value
from Ch1 to Ch10
Setting range: See “Temperature
alarm” in Chapter 11. Specifications
(Page.93)
Alarm 2 (Low limit) set value
from Ch1 to Ch10
Setting range: See “Temperature
alarm” in Chapter 11. Specifications
(Page.93)
Main output proportional cycle setting
from Ch1 to Ch10
Setting range: 1 to 120 sec.
Heater burnout alarm setting
from Ch1 to Ch10
Setting range: 0.0 to 20.0A [W(20A)]
0.0 to 50.0A [W(50A)]
52