Download C SERIES
Transcript
9.9 Alarm 1 (A1), Alarm 2 (A2) action High limit alarm action High limit alarm with standby Hysteresis Status bit Hysteresis Status bit 1 ON 1 ON 0 OFF 0 OFF Alarm setting Main setting Main setting Low limit alarm action Low limit alarm with standby Hysteresis Status bit Status bit ON 1 Alarm setting ON OFF Alarm setting High/Low limits alarm action Status bit 1 ON 1 0 OFF 0 Main setting Hysteresis ON OFF Alarm setting Alarm setting High/Low limit range alarm action Alarm setting Main setting High/Low limit range alarm with standby Hysteresis Status bit Main setting High/Low limits alarm with standby Hysteresis Alarm setting Hysteresis 1 OFF 0 Main setting 0 Status bit Alarm setting Hysteresis Status bit 1 ON 1 ON 0 OFF 0 OFF Alarm Main Alarm setting setting setting Alarm Main Alarm setting setting setting Process high alarm Status bit Process high alarm with standby Hysteresis 1 0 Status bit ON 1 OFF 0 Hysteresis ON OFF Alarm setting Alarm setting Process low alarm with standby Process low alarm Status bit Hysteresis Status bit 1 ON 1 0 OFF 0 Alarm setting Hysteresis ON OFF Alarm setting part: The standby functions. or is the action point that alarm is turned on. Explanation of the alarm action with standby function When the power is initially supplied to the controller, the function disables alarm action even if the input value is in the range in which the alarm action works, and this also prevents the alarm even if the alarm action point enters the above range as a result of the main set value change during control. Once the input value exceeds the alarm action point continuing the control, the standby function will be released and when the input value reaches the point again, the alarm action output will work. 87