Download User`s Manual - Version 02
Transcript
I/O Functional Description 5-23 TRANS 01D % of Velocity Velocity Override 2 Velocity Override 1 Velocity Override Active used (input) (input) (output) 100% 0 0 0 50% 0 1 1 25% 1 0 1 10% 1 1 1 Table 5-15: Velocity Override Inputs and Output The Velocity Override feature is available in TRANS 01-D firmware release 06V39 and later. These inputs were unused (“reserved”) in releases prior to 06V39. 5.10 Cycle Interface Outputs Ready The TRANS 01-D issues the Ready signal to indicate that all conditions are correct for the automatic cycle. Ready will continue to be present on the Cycle Interface as long as all conditions for an automatic cycle remain acceptable. These conditions are: • Automatic Mode selected (connector X17, pin 2 high.) or Manual mode ready parameter P06 is enabled in Manual mode. • Axis normalized (homing performed since power-up or clear). • Block 000 selected. When the Ready line is high, a Start signal from the Line Control will be accepted by the TRANS 01-D, as long as the Enables are also present. Homed The Home output indicates that all enabled slides are in a position where the tool is clear of the workpiece, therefore a part transfer is possible. It is also related to the Home Limit switch, when used, and indicates that the slide is at or behind the Home position. The following conditions must also be satisfied. • Reference position is known (homing done since last reset). The Home outputs are designed to show the user the status of each axis after homing. If only one axis and a Spindle are used, the output on Pin #18 or Interbus-S Object 5F91 will be used. If multiple axes are configured, the output on Pin 18 or Interbus-S Object 5F91 will be an all axis at Home output. If the user requires additional outputs to determine when each axis is at Home, the outputs in Interbus-S Object 5F92 can be used. Note: The Spindle At Home output is not used in the logic for the Home output. No Fault In both Automatic and Manual modes, loss of the Fault output is indicated when the TRANS 01-D has diagnosed a malfunction. This signal indicates that the respective unit is not operational. When a fault occurs, an operator must determine and resolve the problem utilizing the diagnostic display capabilities of the TRANS 01-D, then reset the TRANS 01-D, homing the axis if necessary in order to bring it to Ready status once more. DOK-CONTRL-TRANS01D*06-AW02-AE-P