6 General software functions
6.2.6 Control location
Function
Effect
• The control location determines the
interface for submission of the
control command to start the closedloop control.
• The control location is automatically
set when choosing a preset solution.
• Possible control locations are (see
Table 6.26):
- Terminals
- Control unit
- Serial interface
- Optional slot (PROFIBUS),
- CAN-interface
- PLC
The control location is set with parameter 260-CLSEL (DRIVEMANAGER
function mask "Setpoint/Ramps - further settings“).
DRIVEMANAGER
Value range
WE
Control location for
motor control
OFF ... PLC
TERM
Table 6.24
Unit
1
2
3
4
Parameters
260_CLSEL
(_CONF)
5
Parameter control location
6
Evaluation of start signal
Prerequisites for starting the controller:
• Hardware release ENPO is set at least 10 ms before setting the start
signal (High-Level).
7
• The device status "Safe Stop" (on CDB3000 only with hardware
version "SH“) is inactive.
The start signal is evaluated in dependence on the signal level.
Start "flank triggered“ (factory
setting)
Start "Level triggered" (AutoStart)
Starting takes place after a Low-High transition of the signal. If the start
signal is at High-Level immediately after switching on, the control is not
started. A Low-High transition is required first.
8
A
Starting takes place when the start signal has High-Level. If the start
signal is at High-Level immediately after switching on the mains supply,
the control is started.
The function is also used for automatic starting after switching on the
main supply. It is switched on by parameter 7-AUTO = ON.
Application Manual CDE/CDB/CDF3000