Download "user manual"
Transcript
6 General software functions Setting for parameter MOPTC: BUS DRIVEMANAGER 0 OFF Monitoring switched off 1 KTY linear PTC (KTY84-130, tolerance band yellow) 2 PTC Threshold value PTC with short-circuit detection (DIN 44081/44082) - recommended for "Triple-PTC“ - 3 TSS Klixon (normally closed temperature switch) 41 PTC1 Threshold value PTC without short-circuit detection (DIN 44081/44082) - recommended for "Single-PTC“ - Table 6.34 Function Setting for the type of motor PTC-evaluation MOPTC Specification of temperature sensor connection X3 X3 Specification: • Measuring range max. 12 V • Measuring range 100 Ω - 15 kΩ • Short-circuit detection 18 Ω to 100 Ω • Cycle time 5 ms Explanations • The following temperature sensors can be evaluated: − linear PTC (KTY84-130, tolerance band yellow) − Threshold value PTC (acc. to DIN 44081, DIN 44082) − temperature dependent switch (Klixon) • If the temperature exceeds a limit value, the positioning controller switches the motor off with error message E-OTM. The reaction to the error "Overtemperature motor" can be parameterized. (see chapter 6.9.1). • With "KTY84 -130“-evaluation the actual motor temperature is displayed in the actual value menu (button "Actual values"). • The „KTY84 -130“-evaluation has an adjustable "Motor temperature" warning threshold, to warn in case of an expected overtemperature shut-down (see chapter 6.9.2). • With evaluations by means of KTY84-130 the limit value can be set with parameter 334-MOTMX "Maximum temperature“. Application Manual CDE/CDB/CDF3000 6-84