Download Downloading
Transcript
11-2 <Toc> <Ind> 11.1.2 Possible Errors During Operation The following shows possible errors occurring during operations. Error indication (on PV display unit) Displays “RJC” and PV alternately Description of error RJC error Decimal point of item part EEPROM error in SP display unit blinks. (E300) (B.OUT) ADC error PV Measured with RJC=0 Normal action Control output Normal action Normal action (E200) Auto-tuning failure (Time-out) Action with PID existing before auto-tuning Feedback resistor breakdown Normal action Faulty communication line Power off Normal action None Normal action Check process. Check process. Press any key to erase error indication. Stopped 0% or less or OFF Check wires and sensor. Normal action Normal action Decimal point at right end Runaway (due to lights. defective power Undefined or noise) All indications off Faulty Contact us for repair. In AUTO: Dependent on the Preset value output In MAN: BSL parameter PV burnout error Up-scale: 105% Normal action Down-scale: -5% Excessive PV -5% or 105% Out of -5 to 105% Left end of SP display unit blinks. Remedy 105% (OVER) or (-OVER) Setpoint display unit Alarm Retransmis- Commuoutput sion output nication OFF Stopped Check the feedback resistor. Normal action Check wires and communication parameters, and make resetting. Recovery at normal receipt 0% or less Faulty if power off/on does not reset start the unit. Contact us for Stopped repair. Check for abnormal power. T11-01.EPS TI 05D01C12-01E 1st Edition : Mar. 30, 2001-00