EXPERT VT110 6.2.1.3. Outside Temperature Compensation Stage 1 and 2 bandwidths can be adjusted automatically as a function of outdoor temperature compensation. As the outside temperature decreases, stages 1 and 2 bandwidths increase gradually to compensate for the change. The user specifies the bandwidth used in summer as well as the bandwidth used in winter for both variable outputs of stages 1 and 2. The bandwidths can be adjusted from 1 to 10°F (0.6 to 5.6°C). The winter’s bandwidth must be even or greater than the summer’s bandwidth. Bandwidths of stages 1&2 Bandwidth as a Function of Outside Temperature 6.2.2. Settings 6.2.2.2. Season Change 6.2.2.1. Start/Stop Temperatures If the outside temperature compensation on the bandwidths of stages 1 and 2 is used, you must specify at what outdoor temperature winter and summer start. Note that the start temperature of a fan stage is likely to change if the set point changes or if the bandwidth changes according to the outside temperature. »» START / STOP TEMPS »» 9. Outdoor Comp.* 1. Select: »» START / STOP TEMPS »» 2. Fan Stages Ventilation Stage 1 On Var1 bandwidth Var2 bandwidth 70.0 2.0 2.0 2. Set the following parameters: (Refer to the previous section to get further information on these parameters) Winter Bandwidth On & Off Temperatures — Set the start and stop temperatures of each fan stage. Summer Bandwidth Winter T° Summer T° Outside T° Note that the ventilation stages’ start temperatures will be adjusted following the bandwidth fluctuations as the outside temperature changes. 1. Select: Notes: Stage 1 stops when the room temperature falls 0.3 °F below its start temperature. *This menu is accessible if the outside compensation on stages 1-2 is enabled (sec. 4.5). Outdoor Compensation Summer Temp. 60.0 Winter Temp. 50.0 2. Set the following parameters: Summer Temp. — Set the outside temperature at and above which summer bandwidths must be used. Winter Temp. — Set the outside temperature below which winter bandwidths must be used. The minimum difference between two consecutive start temperatures is of 0.5 °F (0.3 °C). The start temperature of a fan stage must be greater value than its stop temperature. Var1 & Var2 bandwidth — Set the number of degrees required for variable fans to reach their full speed in stages 1 and 2. If the “Outside temperature compensation” function is used, set these bandwidths separately for winter and for summer (see sec. 4.5). EXPERT VT110 rev.15 17