Download EXPERT VT110
Transcript
EXPERT VT110 7. HEATING 7.2. 0-10V Heater 7.1. Heating Stages The controller can control two independent heating stages. These stages are independent from one another and each operate according to their own temperature settings and probe selection. The stop temperature of an heating stage must be at least 0.5°F (0.3°C) higher than its start temperature. The start (On) temperature can be set from 0.5°F (0.3°F) below the set point to -40°F (-40°C). Output Status Operating Diagram of a Heating Output The controller has two 0-10V outputs that can either be used to control heaters or fans. To operate these outputs, the controller refers to the average temperature reading of their assigned temperature probes (see sec. 4.7.3). This section explains how a 0-10V heater work. Intensity (%) On T° Off T° T° of heater's probes 1. Select: »» START / STOP TEMPS »» 1. Heaters Heaters Heater 2 On Heater 2 Off Heater 1 On 67.0 68.1 69.0 2. Set the following parameters: Heater X On/Off — Set the temperature at which each heating stage starts and stops. 26 EXPERT VT110 rev.15 »» 4. 0-10V Outputs »» Select the desired 0-10V Output * This menu is accessible if a 0-10V output is enabled (sec. 4.5). Max 2. Set the following parameters: Min Start temperature — Set the start temperature to the desired value. Max T° Off »» START / STOP TEMPS Start Temp 75.0°F Min: 10 Max: 100 Max Output at: 72.5 Stop at: 70.0 0-10V Heater Off On 1. Select: Start T° Stop T° T° of 0-10V heater probes The 0-10V heater start at their minimum intensity when the temperature falls below the start temperature of the output. The intensity of the heater increases as the temperature decreases; the maximum intensity is reached when the temperature falls below the Max. Temperature parameter setting. Minimum & max speeds — Set the minimum and maximum speeds of the 0-10V output. The maximum speed must be greater than the minimum speed. Maximum output at — Set the temperature at which the output reaches its maximum speed (this parameter must smaller than the start temperature). Stop at — This is the temperature below which the 0-10V output stops.