Figure 7 The control signal of air demand with set point Terminal Standard Standard settings* configuration Standard function Out(1) 0-10VDC 600-900 ppm CO2 o 23-24 C o Cut off 18-17 C Air control alt 1 Out(2) 0-10VDC 600-900 ppm CO2 Air control alt 2 Relay Closed Open >600 ppm CO2 < 500 ppm CO2 Air control alt 3 Out(4) 0-10 VDC 20-18 C o Configuration of this sensor Settings of this sensor Heat control Table I. Default configuration of aSENSE VAV. Function description in details with all parameter settings is in a separate document. Formulas for calculation of output values Configuration Output Range Formula for calculation 0-10 VDC 0-2000 ppm CO2 CO2 value = Volt/10*2000 o 2-10 VDC Temperature value in C = Volt/10*50 0-2000 ppm CO2 CO2 value = (Volt –2)/8*2000 o 4-20 mA o 0-50 C Temperature value in C = (Volt –2)/8*50 0-2000 ppm CO2 CO2 value = (mA-4)*2000/16 o 0-50 C a-b o 0-50 C o Temperature value in C = (mA-4)*50/16 c–d Value = (reading-a)/(b-a)*(d-c)+c a = lowest value of the configuration b = highest value of the configuration c = lowest value of the range d = highest value of the range Table II. Calculation of CO2 value and temperature value for aSENSE VAV Document Rev Page 4 (18)