The Multi-Application Control Plugin 4. 14 If a liquid pressure sensor is connected, set the following settings: Setting Description Range The pressure range that the sensor is capable of. Select DISABLED to disable the sensor. High Alarm If the liquid pressure sensor detects a pressure that is higher than this, a warning appears. Low Alarm If the liquid pressure sensor detects a pressure that is lower than this, a warning appears. High Alarm Delay You can set a delay so momentary changes in pressure do not trigger the warning. The High Alarm warning will not appear until the High Alarm limit has been reached for this length of time. Low Alarm Delay You can set a delay so momentary changes in pressure do not trigger the warning. The Low Alarm warning will not appear until the Low Alarm limit has been reached for this length of time. AgGPS FieldManager Display User Guide 3 29