Power Share Management
The menu will be present only if the feature is supported by the UPS.
The UPS can have up to 4 power plugs.
The power plugs are programmable outlets that can vary their output behaviour as the
user decides.
This menu lets you configure the behaviour of the output plugs (see Figure 4.6).
Available Plugs :
Lists the Active Plugs. If a plug is not available, the related line is hidden.
Mode :
Management Off :
The automatic plugs management is disabled.
Remaining Battery Capacity Management :
The output power plug will be switched off when the Battery Capacity is lower than the
set value (1 to 99%). This feature is managed by the UPS.
Remaining Backup Time Management :
The output power plug will be switched off when the Remaining Backup Time is lower
than the set value (1 to 120 minutes).
This feature is managed by the UPS.
Emergency Light :
In case of mains failure, the UPS closes the plug(s) to supply the emergency lights.
When the power is restored, the plug will be opened (no value setting).
This feature is managed by the UPS.
Value :
Value used to manage the power share plugs.