Download Starting UNI VISION
Transcript
Shutdown Procedure for Windows NT4.0 and 2000 By default UNI VISION is not configured to send shutdown commands. On Windows™ NT4.0, Windows™ 2000 you can use the “SHUTDOWN” application supplied with UNI VISION. If you need more information about the “SHUTDOWN” command, please type “SHUTDOWN /?” at the command shell prompt, a popup window will appear (see Figure C.2). Figure C.2 SHUTDOWN.EXE Parameters For details on how to configure the Shutdown command, see “Prg Parameters” in Chapter 4 : Accessing UNI VISION via Web Browser. For the server shutdown procedure, it may be necessary to specify the full path for the “SHUTDOWN” command, changing the default syntax from “SHUTDOWN /C /L /T:5” to “ programfolder \SHUTDOWN /C /L /T:5” I.E. “C:\Program Files\Socomec Sicon Ups\UniVision\SHUTDOWN /C /L /T:5” If “C:\Program Files\Socomec Sicon Ups\UniVision\” is the folder where Uni Vision has been deployed. 65