2 2 The AXM LD OFB Internal Operation External view The EXEC AXM LD instruction starts the transfer sequence if the OFB is not already being executed. While this sequence is being run, the AXM LD, READY and AXM LD, ERROR bits are set to 0. Once the transfer is complete, the AXM LD, READY bit is reset to 1 and the AXM LD, ERROR bit is set to 1 if the transfer was unsuccessful. The AXM LD Status variable allows the user to identify the type of problem encountered. Transfer duration C 3 AXM LD, READY AXM LD, ERROR EXEC AXM LD INSTRUCTION or set LOAD bit to 1 (1) The module is not reset to Run by the OFB It is up to the user to do this once the transfer is complete, i.e. when the AXM LD, READY bit changes from 0 ¿ 1 on condition that the ERROR bit is at 0. If the EXEC AXM LD instruction is encountered again while a transfer is in progress, it is ignored. It is up to the user to ensure that the EXEC AXM LD instruction is only scanned once in a program. This instruction should be conditional on an event that will only occur once during a PLC cycle (bit SY0, SY1, rising edge, etc.). (1) Using PL7-3 (in DATA mode) or SYSDIAG. 2/8