Preparation and Inspection Chapter 2 5. Switch the miniature circuit breakers in the LV Cabinet off. Figure 4 - Control Switches Miniature Circuit Breakers 6. Switch the miniature circuit breakers in the Isolation Transformer Cabinet LV Control panel off. Switch the Top Main Cooling Fan circuit breakers off. Figure 5 - Control Switches Top Main Cooling Fan Circuit Breakers Miniature Circuit Breakers 7. Remove two star connection cables (the cabling that goes through the HECS) and connect them to the output connections of any two power modules within a phase. Figure 6 - Star Connection Cable Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 25