Download Temperature Control Module User`s Manual
Transcript
3 SPECIFICATIONS MELSEC-Q (b) Auto tuning operation Auto tuning performs operation as shown below. 1) Auto tuning output is provided. 2) Data collection starts when the process value returns to the set value after the first overshoot and undershoot. 3) After data collection, auto tuning ends when PID constants and loop disconnection detection judgment time are set. Process value (PV) The first overshoot and undershoot are ignored. End of auto tuning Set value (SV) (Temperature set value) Start of auto tuning Time Data collection Auto tuning in execution Temperature control ON OFF Yn4,Yn5,Yn6,Yn7 ON Xn4,Xn5,Xn6,Xn7 OFF (c) Precautions for auto tuning The following indicate the conditions under which auto tuning will result in abnormal termination. 1) The buffer memory addresses of the corresponding channels have been changed. 2) The forced PID control stop command (YnC to YnF) was turned on. 3) The setting/operation mode command (Yn1) was turned off. (Except when the PID continuation flag (buffer memory address: A9H) is "Continue") 4) Switched to the Manual mode (MAN). 5) A hardware error occurred. 6) The temperature process value (PV) fell out of the input range. 3-7 3-7