Download Application manual - Amazon Web Services
Transcript
Section 3 IED application 1MRK504089-UEN C Disconnectors and earthing switches have a limited switching capacity. Disconnectors may therefore only operate: • • With basically zero current. The circuit is open on one side and has a small extension. The capacitive current is small (for example, < 5A) and power transformers with inrush current are not allowed. To connect or disconnect a parallel circuit carrying load current. The switching voltage across the open contacts is thus virtually zero, thanks to the parallel circuit (for example, < 1% of rated voltage). Paralleling of power transformers is not allowed. Earthing switches are allowed to connect and disconnect earthing of isolated points. Due to capacitive or inductive coupling there may be some voltage (for example < 40% of rated voltage) before earthing and some current (for example < 100A) after earthing of a line. Circuit breakers are usually not interlocked. Closing is only interlocked against running disconnectors in the same bay, and the bus-coupler opening is interlocked during a busbar transfer. The positions of all switching devices in a bay and from some other bays determine the conditions for operational interlocking. Conditions from other stations are usually not available. Therefore, a line earthing switch is usually not fully interlocked. The operator must be convinced that the line is not energized from the other side before closing the earthing switch. As an option, a voltage indication can be used for interlocking. Take care to avoid a dangerous enable condition at the loss of a VT secondary voltage, for example, because of a blown fuse. The switch positions used by the operational interlocking logic are obtained from auxiliary contacts or position sensors. For each end position (open or closed) a true indication is needed - thus forming a double indication. The apparatus control function continuously checks its consistency. If neither condition is high (1 or TRUE), the switch may be in an intermediate position, for example, moving. This dynamic state may continue for some time, which in the case of disconnectors may be up to 10 seconds. Should both indications stay low for a longer period, the position indication will be interpreted as unknown. If both indications stay high, something is wrong, and the state is again treated as unknown. In both cases an alarm is sent to the operator. Indications from position sensors shall be self-checked and system faults indicated by a fault signal. In the interlocking logic, the signals are used to avoid dangerous enable or release conditions. When the switching state of a switching device cannot be determined operation is not permitted. For switches with an individual operation gear per phase, the evaluation must consider possible phase discrepancies. This is done with the aid of an ANDfunction for all three phases in each apparatus for both open and close indications. Phase discrepancies will result in an unknown double indication state. 412 Application manual
Related documents
Application Manual
Maintenance Assistant RAD
Commissioning manual, Generator protection REG650 1.2, ANSI
BROADWAY BIG BAND – USER`S MANUAL V1.06
PHOIBOS
Entreprises
fulltext - DiVA Portal
TICRO 100 - Application Note - All
Application Manual
Viking ATA-100 Datasheet
Yard Machines 650 Series Technical data
Viking Technology PSF1XXXXGXXXX Computer Drive User Manual
IEC 61850 Communication protocol manual
Vastera VA-103 Installation manual
Currier Tech 650CD Series Technical data
Les Formations Ouvertes et à Distance (FOD) Les
IT Services For University Staff.
Agilent Technologies 35670A User's Manual
Brother BES-1216AC Instruction manual
FOD - Portail de la formation en Picardie