Download User Manual - Schneider
Transcript
Operating Modules from the Application Language Objects Associated with Configuration At a Glance The configuration of an analog module is stored in the configuration constants (%KW). The parameters r, m, and c shown in the following tables represent the topologic addressing of the module. Each parameter had the following signification: r: represents the rack number m: represents the position of the module on the rack c: represents the channel number BME AHI 0812, BMX AMI 0410, BMX AMI 0800, and BMX AMI 0810 Configuration Objects and Inputs of BMX AMM 0600 The process control language objects associated to the configuration of the BME AHI 0812, BMX AMI 0410, BMX AMI 0800, and BMX AMI 0810 modules include the following: Addresses Description Bits Meaning %KWr.m.c.0 Channel range configuration Bit 0 to 5: electric range (hexadecimal value) Bit 7: 0=electrical range (always 0) %KWr.m.c.1 Scale/User scaling min value %KWr.m.c.2 Scale/User scaling max value - %KWr.m.c.3 Over range below value - %KWr.m.c.4 Over range above value - %KWr.m.c.5 Channel treatment configuration Bit 0: Bit 1: Bit 2: Bit 7: Bit 8: Bit 9: EAV16400 04/2014 0=Mast mode, 1=Fast mode 0=channel disabled, 1=channel enabled 0=sensor monitor off, 1=sensor monitor on 0=Manufacturer scale, 1=user scale over range lower threshold enabled over range upper threshold enabled 207