Download User Manual - Schneider
Transcript
Diagnostics Detailed Diagnostics by Analog Channel At a Glance The channel diagnostics function displays detected errors when they occur, classified according to category: Internal detected errors inoperative channel calibration detected error External events sensor link event range overflow/underflow Other detected errors configuration detected error communication loss detected application detected error value outside range (output channel) channel not ready A channel detected error is indicated in the Debug tab when the column, turns red. LED, located in the Error Procedure To access the channel detected Fault dialog, follow these steps: Step Action 1 Open the module debugging screen. 2 For the inoperative channel, click the button situated in the Error column. Result: The list of channel detected errors appears. Note: Channel diagnostics information can also be accessed by program (instruction READ_STS). 168 EAV16400 04/2014