Controller BLS1 V 4.x Date 11-2009 MENU BAR OPTIONS Click on “Options" in the upper menu bar to open the drop-down menu: Fig. 6 1. Error 4 mA: Checking this function makes the controller stop if the input-current of an analog 420mA input is below 4 mA (PLC fault, cable breakage, etc.) 2. Valve Release: Checking this function means the controller runs only when +24V is applied to the digital input Valve-Release (this is pin 12z on the card rack). If Valve Release is not checked then, on power outage, the proportional valve(s) will switch off and the system will stop at its current position (see below for further explanation). 3. Open Without Release (only works when Valve Release is checked): Checking this function means the controller runs normally when +24V is applied to the digital input Valve-Release (Pin 12z on the card rack). If you remove the 24V from this input the proportional valve pair will go to its maximum position, following whatever Ramp Up speed has been set. 8 / 38