Download User Manual
Transcript
PQM-701 Operating manual Fig. 23. Power and energy: Energy tab. 5.2.6 Harmonics The Harmonics branch can be used to configure the recording method and event detection for voltage and current harmonics and other parameters directly related to them. The branch has two tabs: Basic and Additional. Basic • • • 62 This tab is shown in Fig. 41. In the top part, the user can choose the voltage or current harmonics. THD (total harmonic distortion) – similarly to other configuration areas, the fields Min, Max, Avg, Inst. are used to set the recording of minimum, maximum, average and instantaneous values according to set averaging period. The event detection can be activated on the righthand side. The event will be recorded when THD exceeds the user-defined threshold value. The event threshold setting range is 0.0…100.0% with 0.1% increment for voltage, and 0.0…200.0% with 0.1% increment for current. Harmonics – here the user decides to activate the recording of harmonic amplitudes and about event detection. The event detection thresholds are settable independently for each harmonic from the 2nd to the 50th order. The setting method is identical as for the harmonics setting according to EN 50160 (see description in section 5.2.2). There is also an additional option of selecting the units of harmonics levels: in absolute units (volts or amperes) or in percent. The event threshold adjustment range is as follows: