Download MVI69-PDPMV1 User Manual
Transcript
MVI69-PDPMV1 ♦ CompactLogix or MicroLogix Platform PROFIBUS DPV1 Master Mailbox Messaging User Manual Command: Message data word 1-63 Byte-array stating which slave/slaves to start. Array index is equal to slave address. 0: Do not affect slave 1: Start slave 2-255: Reserved Response: Message information (in response header) "Invalid Data Size" is returned if Data size in the command header does not equal 126. If "Invalid Other" is returned, further information is to be found in Extended word 8. Additional Fault information (Extended word 7) If Extended word 8 equals 0x000A -"Failed to execute request", additional info can be found here. Fault information (Extended word 8) 0x0001: Invalid setting in Message data word 1-63 of the command. 0x0002: At least one slave reports a warning. Refer to Message data word 163. 0x000A: Failed to execute request. Additional fault information is to be found in Extended word 7. 0x00FF: Module not initialized (this command is only possible after END_INIT). Message data word 1-63 Byte-array stating the status of the slaves. Array index is equal to slave address. 0: Slave unaffected 1: Slave started 2: Warning - Slave could not be started because it is not part of the configuration ProSoft Technology, Inc. July 8, 2011 Page 103 of 225