Download MVI69-PDPMV1 User Manual
Transcript
MVI69-PDPMV1 ♦ CompactLogix or MicroLogix Platform PROFIBUS DPV1 Master Diagnostics and Troubleshooting User Manual 5.1.3 Viewing the Fieldbus Data from the MVI69-PDPMV1’s Configuration/Debug Menu Note: For this procedure, you must connect a serial cable from the serial port on your PC to the RJ45 to DB9M adaptor cable on the MVI69-PDPMV1 module. If your 1769 processor is equipped with a built-in Ethernet port, such as the L32E or L35E processors, you may make a diagnostic connection to the module using CIPconnect. 1 2 3 4 In ProSoft Configuration Builder, select the MVI69-PDPMV1 module, then click the right mouse button to open a shortcut menu. On the shortcut menu, choose DIAGNOSTICS. This action opens the Diagnostics dialog box. Press [?] to display the Main menu, and then press [2] to view Fieldbus data. Note the value in Operation State. If the Master and the slave are communicating correctly, the operation state will be C0 (hex). ProSoft Technology, Inc. July 8, 2011 Page 137 of 225