Download Introduction
Transcript
Communicate with I/O Communicate with FOUNDATION Fieldbus Devices Chapter 5 The 1757-FFLD linking device bridges an EtherNet/IP network to FOUNDATION Fieldbus links. EtherNet/IP Network ControlLogix Controller 1756-FFLD Device FOUNDATION Fieldbus Network 509 -BOD 24vdc T Guideline Description Each 1757-FFLD device supports 16 Logix exchange function blocks. Each Logix exchange function block supports eight analog inputs and eight analog outputs. Each function block uses one CIP connection. One 1756-ENBT communication module supports 125 CIP connections, which in turn supports seven 1757-FFLD devices that each have 16 function blocks. Add another 1756-ENBT module to support additional 1757-FFLD devices. The type of device affects the maximum number of FOUNDATION Fieldbus devices per H1 segment. Each 1757-FFLD device supports two or four H1 segments. Do not exceed the maximum number of virtual communication relationships (VCRs) on each H1 segment. A VCR is a channel that provides for the transfer of data between FOUNDATION Fieldbus devices. The number of VCRs required to send data or receive data depends on the device and type of data. • 8...10 instruments (16 maximum) per each H1 segment. • For valves, 4...6 per segment because valves have more data. The 1757-FFLD supports a maximum of 16 publisher and 16 subscriber VCRs for each H1 segment. Each parameter you pass to or from the Logix5000 controller uses a VCR. Some devices, such as valves, use more VCRs than transmitters. Make sure you have the correct device description (DD) for each FOUNDATION Fieldbus device. DDs are like EDS files for DeviceNet devices. You can find DDs on vendor/organization websites or on media that ships with the device. A host with DD services can interoperate with all parameters defined in the DD for a field device. Use the right wiring and connection products. Always use a tree or modified tree topology. Never daisy chain devices. Noise is the most frequent problem, due to: • wrong wiring. • improper grounding. • bad connectors. To get the best implementation, understand the details of a FOUNDATION Fieldbus system. Publication 1756-RM094C-EN-P - June 2007 See these references: • FOUNDATION Fieldbus Technical Overview at http://www.fieldbus.org • RelcomWiring Guide at http://www.relcominc.com 69