62 As mentioned all the connected clamps will be automatically recognized. Adjust the Currents Probe Info in the applicable sections: Primary & Secondary Transformation Ratios for all the Current channels (As per Clamp's individual Specifications); Nominal Ampere Values for all the Current Channels (Nominal is set for the current measurements that will define PQZIP threshold / tolerance value & it is also used for event settings); Either Reverse the Polarity / maintain it at Normal from the drop-down selection (Polarity toggling is used to correct incorrect wiring) The Behavior Simulation may be reversed 300/3000A Flexible Clamp. Ensure that you adjust the CT Ratio accordingly; The Hardware Range is only applicable for the DC & Custom Clamps. This is adjust according to the Clamp's individual Specifications - See Optional Accessories: