As mentioned all the connected clamps will be automatically recognized. Adjust the Currents
Probe Info in the applicable sections:

Primary & Secondary Transformation Ratios for all the Current channels (As per Clamp's
individual Specifications);

Nominal Ampere Values for all the Current Channels (Nominal is set for the current
measurements that will define PQZIP threshold / tolerance value & it is also used for event
settings);

Either Reverse the Polarity / maintain it at Normal from the drop-down selection (Polarity
toggling is used to correct incorrect wiring)

The Behavior Simulation may be reversed 300/3000A Flexible Clamp. Ensure that you adjust
the CT Ratio accordingly;

The Hardware Range is only applicable for the DC & Custom Clamps. This is adjust according to
the Clamp's individual Specifications - See Optional Accessories: