Download CC-Link IE Field Network Analog-Digital
Transcript
CHAPTER 8 FUNCTIONS 8.17 Error Notification Function When an error, warning, or alarm occurs, the A/D converter module notifies the master station of it using remote input signals and remote registers. Remark The notification of the error, warning, or alarm can be checked on the LED on the front of the module. For details, refer to the following. • PART NAMES ( Page 20, CHAPTER 2) (1) Notification of an error The A/D converter module notifies the master station of an error in the following method. Item Error flag (RXA) Latest error code (RWr0) Description Turns on when a moderate error or major error occurs. An error code is stored when a moderate error or major error occurs. Reference Page 170, Appendix 1.1 (3) Page 177, Appendix 2 (1) (a) Method for clearing an error The method for clearing an error depends on the error type. Error type Major error 8 Clearing an error The error cannot be cleared. Turn on Error clear request flag (RYA) or Initial data setting request flag (RY9) after removing the error cause. (2) Notification of a warning or alarm The A/D converter module notifies that a warning or alarm occurs to the master station in the following method. Item Warning flag (RX7) Latest warning code (RWr1) Description Turns on when a minor error occurs. The error code or alarm code is stored when a minor error occurs. Reference Page 168, Appendix 1.1 (1) Page 177, Appendix 2 (2) 127 8.17 Error Notification Function Moderate error