5530/5520 DataNode Setup
12. Flicker tab
Properties
Flicker (Flicker, MFLKO)
Pst Sample Interval
Plt Sample Interval
Values
Enable Trending (This page)
;
Sample Intervals (minutes)
10
180
Select the journal entry/entries to change
Pst of last complete interval (A)
Pst of last complete interval (B)
Pst of last complete interval (C)
Plt of last complete interval (A)
Plt of last complete interval (B)
Plt of last complete interval (C)
Sliding window Plt calculation (A)
Sliding window Plt calculation (B)
Sliding window Plt calculation (C)
Output 5-Pinst-peak value (A)
Output 5-Pinst-peak value (B)
Output 5-Pinst-peak value (C)
Output 4-1 min TC LPF of Pinst (A)
Output 4-1 min TC LPF of Pinst (B)
Output 4-1 min TC LPF of Pinst (C)
Output 3-square root of Pinst (A)
Output 3-square root of Pinst (B)
Output 3-square root of Pinst (C)
LPF of Output 3 (A)
LPF of Output 3 (B)
LPF of Output 3 (C)
Enable periodic sampling
High-High limit enabled
High-High limit
High limit enabled
High limit
Low limit enabled
Low threshold
Low-Low limit enabled
Low-Low limit
Deadband enabled
Deadband
;
…
0.00
…
0.00
…
0.00
…
0.00
…
0.00
There are three flicker values available for trending: the
Short term flicker or Pst, the long term flicker or Plt, and
Plt calculated on a sliding window. The other parameters
shown above (journal entries) are used primarily for
specialized testing. Flicker measurements are classified per
IEC 1000-4-15.
Under ENABLE TRENDING (THIS PAGE) is a checkbox
in the value field opposite Flicker which enables the
trending of values listed in this page. If the box is checked,
the settings on the page go into effect. Enabling this will
automatically disable the high-frequency dual peak
detectors located in the Transients tab. If the box is not
checked, the remaining settings are persisted but are not in
effect.
Under SAMPLE INTERVALS are two numeric edit
controls: the Pst Interval and the Plt Interval. Pst is
short term perceptibility, used to set the Pst calculation
interval. Typical calculation is over 10 minute interval,
though this can be programmed. Plt is long term
perceptibility, used to set Plt calculation interval. Typical
calculation is over 2 hour interval, though this can also be
programmed. The Plt interval must be an integer multiple
of the Pst interval. Sliding Plt recalculates the Plt value at
each Pst interval, rather than only at the Plt interval.
Under SELECT JOURNAL ENTRY/ENTRIES TO
CHANGE, various flicker parameters can be trended
using periodic readings that are stored in a journal.