Download PC-InfoNode User`s Guide
Transcript
5530/5520 DataNode Setup Demand values are computed as the average value over the demand interval, which can be programmed as a different value than the periodic readings. The following parameter values can be enabled: individual phase and three phase total real power demand, reactive demand, apparent power demand, average PF and peak real power values. Under ENABLE TRENDING (THIS PAGE) is a checkbox in the value field opposite Demand. The box enables the trending of values listed in Demand page. If the box is checked, the settings on the page go into effect. If the box is not checked, the remaining settings are persisted but are not in effect. The following parameter values can be enabled under SELECT THE JOURNAL ENTRY/ENTRIES TO CHANGE: individual phase and three phase total real power demand, reactive demand, apparent power demand, average PF, and peak real power values. Highlight the parameter value you wish to change, then check the Enable periodic sampling box. Check the threshold enable box, and then enter the value for that threshold. Repeat this for all parameters of interest. High limit - specifices an absolute limit for comparison that is higher than the low limit Low limit - specifies an absolute limit for comparison that is lower than the high limit Low-Low limit - specifies an absolute limit for comparison lower than the low limit Deadband limit - specifies how much a value can change before another event is recorded 8 The High-High must be greater than High, Low-Low less than Low. Deadband is the equivalent of sensitivity. The hysteresis values assigned to limits are set by the system. All limit values are used to determine if corresponding reporting or logging action should take place. Note that these limits are the absolute or actual values to trigger on, not a percent of fixed or floating base as can be used in Voltage RMS Variation and Transients limits. For example, if Real Power Demand is detected to cross the threshold limit, then an event is recorded. If the Real Power Demand goes from out of limits to within limits (that is below the high limit minus the hysteresis and above the low limit plus the hysteresis), then the event is recorded. Each parameter has five threshold limits: High-high, High, Low, Low-Low, and Deadband. High-High limit - specifies an absolute limit for comparison that is higher than the high limit 8-13 Signature System InfoNode on PC User’s Guide