11
5571 DataNode Setup
3. Memory tab
Properties
Enabled
Cycles Before
Cycles After
Enabled
Cycles Per Sample
Max. Event Duration (samples)
Cycles to Trigger
Cycles to End
Enabled
Cycles Before
Cycles After
Enabled
Interval (sec.)
Enabled
Interval (sec.)
Enabled
Demand Interval (min.)
Sliding Interval (min.)
Values
Waveform Changes
;
1
4
RMS Events
;
1
512
1
1
Impulses
;
1
4
Snapshots
;
10860
Timeline
;
10860
Demand Report
;
15
{1, 5, 15, 30, 60}
15
{1, 5, 15, 30, 60}
WAVEFORM CHANGES parameters include:
•Enabled: Waveshape (distortion) enabled check box
•Cycles Before: number of cycles before (typically 1)
•Cycles After: number of cycles after (typically 4)
SNAPSHOTS parameters include:
•Enabled: Snapshot (waveforms) enabled check box
•Interval (sec.): interval between recording in seconds
(typ. 10860)
RMS EVENTS parameters include:
•Enabled: RMS variation enabled check box
•Cycles per Sample: cycles per measurement sample
(typically 1)
•Max. Event Duration (samples): maximum event
duration (typ. 512)
•Cycles to Trigger: cycles to trigger (typ. 1)
•Cycles to End: cycles to end (typ. 1)
TIMELINE parameters include:
•Enabled: Timeline (steady state min/max/avg) enabled
check box
•Interval (sec.): interval between recording in seconds
(typ. 900)
IMPULSES parameters include:
•Enabled: Impulses (transients) enabled check box
•Cycles Before: cycles before (typ. 1)
•Cycles After: cycles after (typ. 1)
DEMAND REPORT parameters include:
•Enabled: Demand report (power) check box enabled
•Demand Interval (min.): demand interval in minutes
(typ. 15)
•Sliding Interval (min.): sliding demand interval in minutes (typ. 15)
11-4
Signature System InfoNode on PC User’s Guide